Nominal flow range from 20 L/min to 1500 L/min.
TECHNICAL SPECIFICATIONS:
- Burkert Type 8626
- Item number: 275129 (00275129)
- 8626-26.0M-CH4-E-A -GM84-ALFF-E-12.0
Burkert Type 8626 mass flow meters (MFC) are compact devices that control the mass flow of gases. They regulate the set flow rate regardless of disturbances such as pressure drops or temporary flow resistance. Flow regulators include a flow meter, an electronic module, and a proportional valve. The integrated sensors operate in constant temperature anemometer mode. In this case, the electrical thermal resistance and measuring resistance are set to a constant temperature difference. Both resistors are located directly in the gas flow; three more resistors are located outside it. All resistors are connected in an electrical bridge. The first resistance in the fluid flow measures the fluid temperature. The second, low resistance is constantly heated to maintain a clearly defined excess temperature relative to the fluid temperature. Because the resistors are located directly in the channel, the device has excellent dynamics: the response time when the setpoint or actual value changes is a few hundredths of a millisecond. In addition, the sensor is virtually contamination-free.